167 kva single phase pole mounted transformer/QIANLAI ELECTRIC
Application
The overhead transformer may be used alone for the supply of a single phase load or as one of three units in a bank for the supply of a three phase load. The unit may be direct mounted to a wooden or concrete pole, or cluster mounted on a pole for three phase use.
Our single phase overhead distribution transformer is commonly used in various places including rural areas, remote regions and scattered villages to provide high quality power supply for daily lighting, agricultural production and industrial plants. Aside from these, it is also suitable for the energy saving projects for railway and urban grid.
Standards
IEEE Std C57.12.00™-2000 standard – IEEE Standard for Standard General Requirements for Liquid-Immersed Distribution, Power, and Regulating Transformers
IEEE Std C57.12.01™-2005 standard – IEEE Standard for Overhead-Type Distribution Transformers, 500kVA and Smaller: High Voltage, 34500V and Below; Low Voltage, 7970/13800 V and below
IEEE Std C57.12.31™-2010 standard – IEEE Standard for Pole Mounted Equipment – Enclosure Integrity
IEEE Std C57.12.35™-1998 standard – IEEE Standard for Bar Coding for Distribution Transformers
IEEE Std C57.12.90™-2006 standard – IEEE Standard Test Code for Liquid-Immersed Distribution, Power, and Regulating Transformers
IEEE Std C57.12.91™-2001 standard – IEEE Guide for Loading Mineral-Oil-Immersed Transformers
IEEE Std C57.154™-2012 standard (Pending Approval) – IEEE Standard for the Design, Testing and Application of Liquid-Immersed Distribution, Power and Regulated Transformers using High-Temperature Insulation Systems and Operating at Elevated Temperatures
(ASTM)American Society for Testing Materials
NEMA TR 1-1993 (R2005) – Regulators and Reactors, Table 0-2 Audible Sound Levels10 CFR Part 431 – Department of Energy – Energy Conservation Program for Commercial Equipment: Distribution Transformers Energy Conservation Standards; Final Rule
The corresponding IEC standard is IEC 60076. This standard covers the design, testing, and operational requirements for power transformers. The specific parts are as follows:
IEC 60076-1: Pertains to general requirements and definitions for transformers.
IEC 60076-2: Covers temperature rise tests.
IEC 60076-3: Specifies insulation levels and dielectric tests.IEC 60076-5: Includes requirements for short-circuit withstand capability.
Service condition
- Suitable for both indoor or outdoor
- Air temperature: Maximum temperature: +40℃; Minimum temperature: -25℃
- Humidity: Monthly average humidity 95%; Daily average humidity 90%.
- Altitude above sea level: Maximum installation altitude: 2000m
- Ambient air not apparently polluted by corrosive and flammable gas, vapor etc.
- No frequent violent shake
Note: * Beyond those services condition should enquiry to manufacturer technical dept during order
Rating Details
General technical information is listed below:Information on less common requirements can be obtained through qianlai sale department
Capacity kVA: 3kVA — 167kVA
Temperature rise: 65℃
Cooling type: ONAN
Working Frequency: 50/60Hz
Polarity: additive or Subtractive
Core-type: CRGO or Amorphous
Protection: CSP or not
| Primary voltage | Secondary voltage | |
| Rating (V) | BIL(kV) | 120V/240V 240V/480V 139V/277V 250V/500V |
| 41600-48000 | 75 | |
| 72000-12470 | 95 | |
| 13200-14400 | 125 | |
| 19920-22900 | 150 | |
| 34500 | 200 | |
| capacity (KVA) | primary Rating(KV) | Amorphous core | CRGO core | ||
| No load loss(W) | Load loss(W) | No load loss(W) | Load loss(W) | ||
| 3 | 13.8/7.967KV 13.2/7.62KV 11/6.35KV Or customizable | 8 | 45 | 9 | 45 |
| 5 | 8 | 75 | 19 | 75 | |
| 10 | 12 | 120 | 36 | 120 | |
| 15 | 15 | 195 | 50 | 195 | |
| 25 | 18 | 290 | 80 | 290 | |
| 37.5 | 30 | 360 | 105 | 360 | |
| 50 | 32 | 500 | 135 | 500 | |
| 75 | 45 | 650 | 190 | 650 | |
| 100 | 50 | 850 | 210 | 850 | |
| 167 | 65 | 1410 | 350 | 1410 | |