167 kva single phase distribution transformer

167 kva single phase pole mounted transformer/QIANLAI ELECTRIC

 

Application

The overhead transformer may be used alone for the supply of a single phase load or as one of three units in a bank for the supply of a three phase load. The unit may be direct mounted to a wooden or concrete pole, or cluster mounted on a pole for three phase use.

Our single phase overhead distribution transformer is commonly used in various places including rural areas, remote regions and scattered villages to provide high quality power supply for daily lighting, agricultural production and industrial plants. Aside from these, it is also suitable for the energy saving projects for railway and urban grid.

 

Standards

IEEE Std C57.12.00™-2000 standard – IEEE Standard for Standard General Requirements for Liquid-Immersed Distribution, Power, and Regulating Transformers

IEEE Std C57.12.01™-2005 standard – IEEE Standard for Overhead-Type Distribution Transformers, 500kVA and Smaller: High Voltage, 34500V and Below; Low Voltage, 7970/13800 V and below

IEEE Std C57.12.31™-2010 standard – IEEE Standard for Pole Mounted Equipment – Enclosure Integrity

IEEE Std C57.12.35™-1998 standard – IEEE Standard for Bar Coding for Distribution Transformers

IEEE Std C57.12.90™-2006 standard – IEEE Standard Test Code for Liquid-Immersed Distribution, Power, and Regulating Transformers

IEEE Std C57.12.91™-2001 standard – IEEE Guide for Loading Mineral-Oil-Immersed Transformers

IEEE Std C57.154™-2012 standard (Pending Approval) – IEEE Standard for the Design, Testing and Application of Liquid-Immersed Distribution, Power and Regulated Transformers using High-Temperature Insulation Systems and Operating at Elevated Temperatures

(ASTM)American Society for Testing Materials

NEMA TR 1-1993 (R2005) – Regulators and Reactors, Table 0-2 Audible Sound Levels10 CFR Part 431 – Department of Energy – Energy Conservation Program for Commercial Equipment: Distribution Transformers Energy Conservation Standards; Final Rule

The corresponding IEC standard is IEC 60076. This standard covers the design, testing, and operational requirements for power transformers. The specific parts are as follows:

IEC 60076-1: Pertains to general requirements and definitions for transformers.

IEC 60076-2: Covers temperature rise tests.

IEC 60076-3: Specifies insulation levels and dielectric tests.IEC 60076-5: Includes requirements for short-circuit withstand capability.

 

 

 

 

 

 

 

 

 

Service condition

  1. Suitable for both indoor or outdoor
  2. Air temperature: Maximum temperature: +40℃; Minimum temperature: -25℃
  3. Humidity: Monthly average humidity 95%; Daily average humidity 90%.
  4. Altitude above sea level: Maximum installation altitude: 2000m
  5. Ambient air not apparently polluted by corrosive and flammable gas, vapor etc.
  6. No frequent violent shake

Note: * Beyond those services condition should enquiry to manufacturer technical dept during order

 

Rating Details

General technical information is listed below:Information on less common requirements can be obtained through qianlai sale department

Capacity kVA: 3kVA — 167kVA

Temperature rise: 65℃

Cooling type: ONAN

Working Frequency: 50/60Hz

Polarity: additive or Subtractive

Core-type: CRGO or Amorphous

Protection: CSP or not

 

Primary voltageSecondary voltage
Rating (V)BIL(kV)120V/240V

240V/480V

139V/277V

250V/500V

41600-4800075
72000-1247095
13200-14400125
19920-22900150
34500200

 

 

capacity

(KVA)

primary

Rating(KV)

Amorphous coreCRGO core
No load

loss(W)

Load

loss(W)

No load loss(W)Load

loss(W)

313.8/7.967KV

13.2/7.62KV

11/6.35KV

Or customizable

845945
58751975
101212036120
151519550195
251829080290
37.530360105360
5032500135500
7545650190650
10050850210850
1676514103501410

 