How 11 415v 100kva dry type distribution transformer Operate Safely Under High Temperature Conditions
11 415v 100kva dry type distribution transformer are widely used in urban distribution networks, high-rise buildings and other scenarios due to their characteristics such as flame retardancy and maintenance-free operation. Their temperature protection settings are based on the insulation class as the core, and the typical parameters are shown in the following table:
| Insulation class | Fan start temperature | Fan stop temperature | Over-temperature alarm temperature | Over-temperature trip temperature |
| F class | 95℃ | 75℃ | 110℃ | 130℃ |
| H class | 105℃ | 85℃ | 130℃ | 150℃ |
Fan control logic: By setting a temperature difference control strategy of “starting at 95℃ / stopping at 75℃” (Class F), it can not only avoid frequent start-stop of the fan affecting the equipment life, but also start forced cooling before the winding temperature approaches the critical value, ensuring that the insulation system is in a safe range.
Trip threshold setting: The trip temperature of 130℃ (Class F) corresponds to the thermal aging critical value of its insulation material. When the temperature exceeds this threshold, the winding insulation life will decay exponentially. Emergency trip is the last line of defense to prevent thermal breakdown accidents.
Application tips: In actual operation, the alarm value can be fine-tuned within the range of ±10℃ according to factors such as load characteristics (such as the proportion of impact load) and ventilation conditions, but the adjustment of the trip threshold needs to be verified by insulation life assessment.
11 415v 100kva dry type distribution transformer Technical Parameter
| Rated capacity | 100kva |
| Rated voltage | 6KV/10KV/33KV/35KV/40.5KV |
| model | SCB(10)-750/10/33/0.4KV or SCB(11)-750/10/33/0.4KV or SCB(12)-750/10/33/0.4KV or SCB(13)-750/10/33/0.4KV or SCB(14)-750/10/33/0.4KV or as per requirement |
| type | Dry type (cast resin) |
| No. of phase | 3 |
| Tapping range | ±2X2.5% |
| Vector Group | Dyn11/Yyn0/as per requirement |
| Winding material | Copper/Aluminum |
| Core material | GRGO |
| Cooling method | AN/AF |
| standard | GB 1094/IEC 60076 |
| Winding Temperature Rise | F insulation class(105K) H insulation class(125K) |
| No load loss | 400±15% W or as per requirement |
| Load loss | 1570±15% W or as per requirement |
| Short circuit impedance | 4% |
| shell | Cold-Rolled Steel Sheet(IP20/IP23)/Stainless Steel |