1500 kva 3 phase Electrial oil Immersed transformer

Qianlai Electric, an expert in the manufacturing of transformers, switchgears, and vacuum circuit breakers.Over the past decade or so, we have been continuously refining our production techniques, committed to providing customers with cost-effective products.

When you purchase a transformer from Qianlai Electric, you don’t need to worry about after-sales issues, because they rarely occur.Even if they occasionally arise, we will send experts to fly to your country to solve the problem on-site for you.If you have a need to purchase transformers, please feel free to inquire about the price.

Why must the iron core of a 1500 kva 3 phase Electrial oil Immersed transformer  be grounded?

During the normal operation of a 1500 kva 3 phase Electrial oil Immersed transformer, the electric field formed between the energized windings, leads, and the oil tank is a non-uniform electric field. The iron core and its metal components are all in this electric field. Due to the different potentials induced by static electricity, the floating potentials of the iron core and its metal components are also different. When the potential difference between two points is high enough to break down the insulation between them, spark discharge occurs. This kind of discharge can decompose the transformer oil and damage the solid insulation. To avoid this situation, the iron core and its metal components must be reliably grounded.
The iron core must be grounded at one point. When the iron core or other metal components are grounded at two or more points, a closed loop will be formed between the grounding points, resulting in a circulating current. This current can sometimes be as high as several tens of amperes, which will cause local overheating, lead to oil decomposition, and may even melt the grounding strip and damage the iron core. All these are not allowed. Therefore, the iron core must be grounded, and it must be grounded at one point.

 

1500 kva 3 phase Electrial oil Immersed transformer Main technical Parameter

Rated capacity1500 KVA
Primary voltage33KV/35KV/13.2KV/11KV/10KV/6.3KV/6KV(customizable)
Tap changer±2*2.5/±5
Secondary voltage400V/415V/433V/380V(customizable)
Vector groupDyn11/Yzn11/Yyn0
Number of phaseThree phase
frequency50hz
Temperature rise65K
Short circuit impedance4.0%
No load lossDifferent series(S9,S11,S13,S14),got different loss data
Load loss 75ºCDifferent series(S9,S11,S13,S14),got different loss data
Cooling typeONAN
Oil type25#/45#
standardsIEC 60076-1

 

1500 kva 3 phase Electrial oil Immersed transformer Workshop

 