250 kva Three phase Oil immersed transformer

Product overview

The 250 kVA oil immersed distribution transformer, featuring reliability, energy efficiency and easy maintenance, is ideal for medium and small-sized industrial and commercial applications as well as power distribution network upgrading needs.

Designed specifically for medium-power distribution scenarios, the 250kVA oil immersed transformer adopts high-quality cold-rolled silicon steel sheets and winding made of copper/aluminum conductors with high-insulation oxidation treatment. It combines oil-immersed insulation with natural convection or forced air cooling systems to ensure long-term stable operation.

Compliant with a variety of voltage combinations and connection groups, it is widely used in factories, commercial complexes, residential communities, construction sites and power distribution station renovations.

Main technical Parameter

Rated capacity250 KVA
Primary voltage33KV/35KV/13.2KV/11KV/10KV/6.3KV/6KV(customizable)
Tap changer±2*2.5/±5
Secondary voltage400V/415V/433V/380V(customizable)
Vector groupDyn11/Yzn11/Yyn0
Number of phaseThree phase
frequency50hz
Temperature rise65K
Short circuit impedance4.0%
No load lossDifferent series(S10,S11,S13,S14),got different loss data
Load loss 75ºCDifferent series(S10,S11,S13,S14),got different loss data
Cooling typeONAN
Oil type25#/45#
standardsIEC 60076-1

Standard Values of No-Load Current and Load Loss for 250kVA Three-Phase Oil-Immersed Transformers

The no-load current and load loss of 250kVA three phase oil immersed transformers (10kV/0.4kV, off-circuit tap changing) are mainly governed by GB/T 6451-2015 and GB 20052-2020. The standards vary with different energy efficiency classes and models. All load loss values are measured at 75℃.

Core Standard Parameter Table (10kV/0.4kV, Dyn11/Yyn0)

Energy Efficiency/ModelNo-Load Loss (Po)Load Loss (Pk, at 75℃)No-Load Current (I0)Standard Basis
Energy Efficiency Class 3 (Minimum Allowable Value)≤290W≤3050W≤1.6%GB 20052-2020
Energy Efficiency Class 2≤260W≤2440W≤1.4%GB 20052-2020
Energy Efficiency Class 1≤230W≤2195W≤1.2%GB 20052-2020
Model S11400W3150W1.6%GB/T 6451-2015
Model S13290W3050W1.2%Energy-Saving Design Value
Model S14340W2440W1.0%High-Efficiency Design Value

 

 

Key Notes

  1. No-Load Currentis expressed as a percentage of the rated capacity, reflecting the magnetizing demand of the iron core. High-efficiency models (e.g., S13/S15) feature lower values thanks to the optimization of silicon steel sheets and structural design.
  2. Load Loss, also known as short-circuit loss at 75℃, corresponds to the copper loss of windings under rated current. It is directly related to the conductor cross-sectional area, material, and manufacturing processes.
  3. Allowable Deviation Range: A tolerance of ±15% is permitted for no-load loss and load loss, while a tolerance of ±30% applies to no-load current. All tests shall be conducted in accordance with GB/T 1094.1-2013.
  4. Special Scenarios: Structures such as amorphous alloy cores and wound cores can further reduce Po and I0. Specific values shall be subject to the manufacturer’s technical documents.